某35kV母线三相短路容量为2000MVA,采用6%串联电抗器,计算电容器组容量不超过下列何值时,可不考虑电容器组对短路电流的助增作用,说明理由。
A.100Mvar
B.200Mvar
C.300Mvar
D.400Mvar
查看答案
正确答案: A 答案分析: 解答过程:根据《导体和电器选择设计技术规定》(DL/T5222—2005)附录F第F.7.1条可知,对于采用6%串联电抗器的电容器装置Qc/Sd≤5%时,可以不考虑其对短路电流的影响,由此可得
Qc≤Sd×5%=2000×5%Mvar=100Mva